Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)3 x Hoistway door closers not working, needs repair. Red tagged, removed from service. Re-inspection required 7/6/2022
MO Minimum : Elevators (A) - Hoistways (A)3 x Replace missing pick-up rollers @ top floor hoistway door. Red tagged, removed from service. Re-inspection required 7/6/2022
MO Minimum : Elevators (A) - Hoistways (A)3 Hoistway door closers not working, needs repair or replaced. 5/2/2023
MO Minimum : Elevators (A) - Hoistways (A)3 Replace missing pickup rollers at top hoistway door 5/2/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. Re-inspection required 1/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A copy of the MCP shall be kept in the machine room for each elevator. 5/2/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 5/3/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements x Generator in machine room shaking due to internal malfunction and won't run car at rated speed, needs repaired. Red tagged, Removed from service. Re-inspection required 7/6/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A copy of the MCP shall be kept in the machine room for each elevator 5/3/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Provide pit light that works 5/2/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) x Provide working elevator pit lights. Red tagged & removed from service. Re-inspection required 7/6/2022
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Test car safeties, rated speed, rated load. Red tagged, removed from service. Re-inspection required 7/6/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x x Test fire service. Red tagged, removed from service. Re-inspection required 7/6/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Smoke detector system not in place, provide same and test with elevator system. Re-inspection required. 1/29/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 5/3/2024