MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
G(1)/A17.1-2016:8.6.1.4 :Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) .
|
8/5/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
G/2.7.1/8.6.1.6.5: Machine Room Fire Extinguisher : shall have an extinguisher in elevator machine space.
|
8/5/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
H(2) Machine space will be separated from other equipment by a substantial fence/gate, no less than 6ft tall. ((Currently open area being used by construction workers as storage area. ))
|
8/5/2022
|