Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Replace the wrong installed smoke detectors that will recall the elevator when activated. 10/4/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Provide a class B rated roof assembly of 2 hour U.L. rating per IBC 10/4/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Fill in the block above the hoistway door to provide a 2 hour rated assembly 10/4/2022