Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.4 - Machine space 2.8.1 x Pipe in machine room; remove or enclose. 5/25/2023
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x 2.8.3.1.2 - Pipes (PVC and black iron) located at the top of the hoistway shall be removed or enclose hoistway with the proper fire rating material. 5/25/2023
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x 2.1.1.2.2 - The 4 x 4 access hatchway at the top of the hoistway shall be enclosed or receive approval from the State of Missouri Compliance Inspection Manager. 5/25/2023
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 x 2.1.6.2 - Bevel all ledges in the hoistway at an angle not less than 75 degrees. 5/25/2023
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x 2.1.1.2.2 - Enclose hole in the hoistway between lower level and the lobby. 5/25/2023
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x 2.8.3.4 - Pipe in the pit at the back wall, right side shall be removed or enclosed. 5/25/2023
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x 2.8.3.4 - Pipe in the pit at the back wall, left side shall be removed or enclosed. 5/25/2023
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x 2.1.1.2.2 & 2.1.6.2 - Enclose the wall behind the counterweight guard and bevel edge. 5/25/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 x 2.8.2.2 - Remove the non elevator switches at the rear of the pit and enclose. 5/25/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x The violations from this inspection were discovered during the temporary use inspection. Additional violations may be cited before the final acceptance. 5/25/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 12/4/2024