Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unintended motion in the up direction needs to be tested. 4/28/2026
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No 2.1.1.2.2 - Enclose hole in the hoistway between lower level and the lobby. 5/25/2023
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No 2.1.1.2.2 - The 4 x 4 access hatchway at the top of the hoistway shall be enclosed or receive approval from the State of Missouri Compliance Inspection Manager. 5/25/2023
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No 2.1.1.2.2 & 2.1.6.2 - Enclose the wall behind the counterweight guard and bevel edge. 5/25/2023
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 Yes No 2.1.6.2 - Bevel all ledges in the hoistway at an angle not less than 75 degrees. 5/25/2023
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Yes No 2.8.3.1.2 - Pipes (PVC and black iron) located at the top of the hoistway shall be removed or enclose hoistway with the proper fire rating material. 5/25/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 Yes No 2.8.2.2 - Remove the non elevator switches at the rear of the pit and enclose. 5/25/2023
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Yes No 2.8.3.4 - Pipe in the pit at the back wall, right side shall be removed or enclosed. 5/25/2023
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Yes No 2.8.3.4 - Pipe in the pit at the back wall, left side shall be removed or enclosed. 5/25/2023
A17.1-2016 : Elevators 2.4 - Machine space 2.8.1 Yes No Pipe in machine room; remove or enclose. 5/25/2023
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current MO State operating certificate shall be displayed in the equipment room in a non-combustible frame. 4/28/2026
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current MO State operating certificate shall be displayed in the equipment room in a non-combustible frame.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test Yes No The violations from this inspection were discovered during the temporary use inspection. Additional violations may be cited before the final acceptance. 5/25/2023
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.10.2.2.2(l) No No Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. 4/28/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No Fire service testing must be documented monthly, the form is present in the MCP, but hass not been logged monthly.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No Fire service testing must be documented monthly, the form is present in the MCP, but hass not been logged monthly. 4/28/2026
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 12/4/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit shall be kep clean. Remove excess dabris.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit shall be kep clean. Remove excess dabris. 4/28/2026