|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
2.1.1.2.2 & 2.1.6.2 - Enclose the wall behind the counterweight guard and bevel edge.
|
5/25/2023
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
2.1.1.2.2 - Enclose hole in the hoistway between lower level and the lobby.
|
5/25/2023
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
2.1.1.2.2 - The 4 x 4 access hatchway at the top of the hoistway shall be enclosed or receive approval from the State of Missouri Compliance Inspection Manager.
|
5/25/2023
|
|
A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.1.6
|
x
|
|
2.1.6.2 - Bevel all ledges in the hoistway at an angle not less than 75 degrees.
|
5/25/2023
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.8
|
x
|
|
2.8.2.2 - Remove the non elevator switches at the rear of the pit and enclose.
|
5/25/2023
|
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
2.8.3.1.2 - Pipes (PVC and black iron) located at the top of the hoistway shall be removed or enclose hoistway with the proper fire rating material.
|
5/25/2023
|
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
2.8.3.4 - Pipe in the pit at the back wall, left side shall be removed or enclosed.
|
5/25/2023
|
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
2.8.3.4 - Pipe in the pit at the back wall, right side shall be removed or enclosed.
|
5/25/2023
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current MO State operating certificate shall be displayed in the equipment room in a non-combustible frame.
|
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Fire service testing must be documented monthly, the form is present in the MCP, but hass not been logged monthly.
|
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.10.2.2.2(l)
|
|
|
Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag.
|
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.8.1
|
x
|
|
Pipe in machine room; remove or enclose.
|
5/25/2023
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Pit shall be kep clean. Remove excess dabris.
|
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
12/4/2024
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.10 Acceptance Inspection and Test
|
x
|
|
The violations from this inspection were discovered during the temporary use inspection. Additional violations may be cited before the final acceptance.
|
5/25/2023
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Unintended motion in the up direction needs to be tested.
|
|