Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.14 - Code data plate 8.9 Yes No A17.1 Section 8.9.1 An Individual Data Tag shall be provided and maintained for each unit. 10/24/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 Yes No A17.1 2.7.9.1 Permanently installed electric Lighting shall be provided in all Machine Spaces, Illumination shall not be less than 19(fc). A light switch shall b e provided at entry level. 10/24/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Yes No 8.10.2.2.2(g) Inspection and Testing panel per 2.26.4.1(d) the Elevator Car Safety Circuit contact points for testing have not been brought to the Controller test points to verify contact devices. The point of verification has not been identified in Controller. 10/24/2022
A17.1-2016 : Elevators 3.1 - Top-of-car stop switch 2.26.2.8 Yes No Stop Switch on Top of Car shall be provided conforming to 2.26.2.5(a)(b) and (c). 10/24/2022
A17.1-2016 : Elevators 4.4 - Hoistway door locking devices 2.12.2.5 Yes Yes Elevator Retiring Cam Device Failed, the Electrical Operational Contacts required by the Cam to operate had been jumped out. Red Tag was required per A17.1 2016 8.10.1.4. 10/24/2022
A17.1-2016 : Elevators 4.5 - Access to Hoistway 2.12.6 Yes No A17.1 Section 2.12.6.1 Access to Hoist way for Emergency purposes shall be at all landings A17.1- 5.7.8.3 requires Access points minimum at Bottome l & Top Landings. Presently there are no access provisions at any landings. 10/24/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 No No Access to pit requires a pit ladder, pit depth is 45 inches per 2.2.4.2 pit greater than 35 inches requires pit ladder.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 No No A permanent lighting fixture shall be provided in compliance with 2.2.5.1-2.2.5.3. Note: Existing Electrical Devices are in Explosion Proof Flex & Conduit.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.3 Yes No Pit Construction A17.1 2.2.2.3 requires a permanent provision to prevent accurance of ground water in the pit. 10/24/2022
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 Yes No A17.1 Section 2.4 item 2.4.2.2 requires a min counterweight runby of 9 inches for elevators with spring buffers which operate at 100 fpm. Hoist ropes require shortening. 10/24/2022