A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
Yes
|
No
|
8.10.2.2.2(g) Inspection and Testing panel per 2.26.4.1(d) the Elevator Car Safety Circuit contact points for testing have not been brought to the Controller test points to verify contact devices. The point of verification has not been identified in Controller.
|
10/24/2022
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
No
|
No
|
A permanent lighting fixture shall be provided in compliance with 2.2.5.1-2.2.5.3. Note: Existing Electrical Devices are in Explosion Proof Flex & Conduit.
|
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
Yes
|
No
|
A17.1 2.7.9.1 Permanently installed electric Lighting shall be provided in all Machine Spaces, Illumination shall not be less than 19(fc). A light switch shall b e provided at entry level.
|
10/24/2022
|
|
A17.1-2016 : Elevators
|
4.5 - Access to Hoistway
|
2.12.6
|
Yes
|
No
|
A17.1 Section 2.12.6.1 Access to Hoist way for Emergency purposes shall be at all landings A17.1- 5.7.8.3 requires Access points minimum at Bottome l & Top Landings. Presently there are no access provisions at any landings.
|
10/24/2022
|
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.2
|
Yes
|
No
|
A17.1 Section 2.4 item 2.4.2.2 requires a min counterweight runby of 9 inches for elevators with spring buffers which operate at 100 fpm. Hoist ropes require shortening.
|
10/24/2022
|
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.9
|
Yes
|
No
|
A17.1 Section 8.9.1 An Individual Data Tag shall be provided and maintained for each unit.
|
10/24/2022
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.4
|
No
|
No
|
Access to pit requires a pit ladder, pit depth is 45 inches per 2.2.4.2 pit greater than 35 inches requires pit ladder.
|
|
|
A17.1-2016 : Elevators
|
4.4 - Hoistway door locking devices
|
2.12.2.5
|
Yes
|
Yes
|
Elevator Retiring Cam Device Failed, the Electrical Operational Contacts required by the Cam to operate had been jumped out. Red Tag was required per A17.1 2016 8.10.1.4.
|
10/24/2022
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.3
|
Yes
|
No
|
Pit Construction A17.1 2.2.2.3 requires a permanent provision to prevent accurance of ground water in the pit.
|
10/24/2022
|
|
A17.1-2016 : Elevators
|
3.1 - Top-of-car stop switch
|
2.26.2.8
|
Yes
|
No
|
Stop Switch on Top of Car shall be provided conforming to 2.26.2.5(a)(b) and (c).
|
10/24/2022
|