A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
2.27.2.3 requires visual notification signal @ main landing fixture.
|
10/5/2022
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Must make emergency phone operable. 1.6
|
8/29/2024
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
3.7.1
|
x
|
|
2.7.3.4.1(a)(b)(c) Machine room door shall be self-closing self-locking kept closed & locked.
|
10/5/2022
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
Type ABC Fire Extinguisher shall be permanently installed in the elevator machine room.
|
10/5/2022
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Item 2.1.6 Hoist way enclosure shall be smooth. Remove exposed shaft liner screw tips.
|
10/5/2022
|
A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.1.6
|
x
|
|
Item 2.1.6.2(c) Beam pocket setbacks more than 4 inches shall have a 75 deg bevel.
|
10/5/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.9 Elevator Corridor Call Station Pictograph
|
x
|
|
Each Elevator landing shall have the signage. In Case of Fire Elevator out of Service Use Stairs.
|
10/5/2022
|