Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x 2.27.2.3 requires visual notification signal @ main landing fixture. 10/5/2022
A17.1-2016 : Elevators 2.1 - Access to machine space 3.7.1 x 2.7.3.4.1(a)(b)(c) Machine room door shall be self-closing self-locking kept closed & locked. 10/5/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph x Each Elevator landing shall have the signage. In Case of Fire Elevator out of Service Use Stairs. 10/5/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Item 2.1.6 Hoist way enclosure shall be smooth. Remove exposed shaft liner screw tips. 10/5/2022
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 x Item 2.1.6.2(c) Beam pocket setbacks more than 4 inches shall have a 75 deg bevel. 10/5/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must make emergency phone operable. 1.6 8/29/2024
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Type ABC Fire Extinguisher shall be permanently installed in the elevator machine room. 10/5/2022