A17.1-2016 : Elevators 2.1 - Access to machine space 3.7.1 Yes No 2.7.3.4.1(a)(b)(c) Machine room door shall be self-closing & locking kept closed & locked. 10/5/2022
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Yes No Type ABC Fire Extinguisher shall be permanently mounted in the elevator machine room. 10/5/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 Yes No 2.27.2.3 requires visual notification signal at main landing fixture. 10/5/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No Item 2.1.6 Hoist way enclosure shall be smooth, remove exposed shaft liner screw tips. 10/5/2022
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 Yes No Item 2.1.6.2(c) Beam pocket setbacks more than 4 inches shall be beveled not less than 75 deg from horizontal. 10/5/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph Yes No Each Elevator landing shall have the signage In Case of Fire Elevators are Out of Service Use Stairs. 10/5/2022
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space No No Must not store none elevator equipment in the Machine Room. 8.6.4.8