A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
|
|
Maintenance Control Program shall be provided and kept on site
|
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Pit needs cleaned
|
|
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
x
|
|
Lobby sill is not level.
|
6/7/2023
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work.
|
6/7/2023
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
All heat and smoke detectors shall be tested.
|
6/7/2023
|
|
A17.1-2016 : Elevators
|
3.14 - Hoistway clearances
|
2.4
|
x
|
|
The beam in the overhead shall be marked as low clearance and designated by striping per code.
|
6/7/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
All suspension tags and governor tags shall be installed.
|
6/7/2023
|