Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x All heat and smoke detectors shall be tested. 6/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x All suspension tags and governor tags shall be installed. 6/7/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 6/7/2023
A17.1-2016 : Elevators 1.4 - Sills and car floor 2.11.11.1 x Lobby sill is not level. 6/7/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation Maintenance Control Program shall be provided and kept on site
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit needs cleaned
A17.1-2016 : Elevators 3.14 - Hoistway clearances 2.4 x The beam in the overhead shall be marked as low clearance and designated by striping per code. 6/7/2023