Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Alarm bell in elevator doesn't work 8/25/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 Car door closing force exceeds 30 lbs
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems The Fire tabs on the gibs need to be bent down to engage with the sill
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Check pump unit or machine for oil leak and repair
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Repair lights in machine room
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 x At the bottom landing, the gap where the two hoistway door panels meet shall not exceed 3/8" 8/21/2024
conversion conversion n/a 2) Exposed live parts of motors and controllers operating at 50 volts or more between terminals shall be guarded against accidental contact by enclosure. The breaker enclosure inner panel is not in place. (Protection of Live Parts) 11/8/2018
conversion conversion n/a 1) The depth of the working space in the direction of live parts shall not be less than that specified in Table 110.26(A)(1). Distances shall be measured from the exposed live parts or from the enclosure or opening if the live parts are enclosed. Minimum distance is not being met for electrical panel which houses breaker for elevator. Will require a variance. 11/8/2018