A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
The emergency/standby power shall be tested.
|
8/27/2024
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Increase machine space to 19 ft-candles minimum
|
5/11/2023
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Increase control space illumination to 19 ft-candles minimum
|
5/11/2023
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
An ABC fire extinguisher with a current test tag shall be mounted convient to the machine room door.
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
x
|
|
Provide shunt trip for mainline disconnect. Activated by heat detector.
|
5/11/2023
|
A17.1-2016 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
x
|
|
Provide a means of smoke control in the hoistway compliant with the building code
|
5/11/2023
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3
|
x
|
x
|
When the car is on phase two fire service and at a landing, with the doors open, and the "FIRE OPERATION" switch is in the "HOLD" position, the car shall remain at the landing with the doors open. Note: Currently when phase two hold operation is selected, the car doors close and the elevator runs to the primary floor of egress. This shall be corrected within 14 days. Not currently red tagged as there are only 2 elevators in this facility and 300 apartment units.
|
8/27/2024
|