A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
|
|
Compliant/required documentation shall be kept on-site including MCP wiring diagrams, PM log, callback log, and evacuation procedures. No such documentation on-site for 2023, 2024, and 2025.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Increase machine space illumination to 19 ft-candles minimum
|
5/11/2023
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Increase machine space lighting to 19 ft-candles minimum
|
5/11/2023
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
x
|
|
Provide shunt trip for mainline. Activated by a heat detector
|
5/11/2023
|
A17.1-2016 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
x
|
|
Provide a means of smoke control in the hoistway compliant with the building code
|
5/11/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
The emergency/standby power shall be tested.
|
8/27/2024
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
2.7.6.3.4
|
x
|
|
The remote governor tripping/reset means on the controller (means to test) shall be operational.
|
8/27/2024
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
2.7.6.3.4
|
x
|
|
The remote governor tripping/reset means on the controller (means to test) shall be operational.
|
11/25/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
The emergency power jewel at main lobby does not illuminate when emergency power operation is enabled.
|
12/3/2024
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
An ABC fire extinguisher with a current test tag shall be mounted convient to the machine room door.
|
12/3/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Elevators equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power annually.
|
5/22/2025
|