Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 An ABC fire extinguisher with a current test tag shall be mounted convient to the machine room door.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The emergency power jewel at main lobby does not illuminate when emergency power operation is enabled.
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 2.7.6.3.4 x The remote governor tripping/reset means on the controller (means to test) shall be operational. 8/27/2024
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 2.7.6.3.4 x The remote governor tripping/reset means on the controller (means to test) shall be operational. 11/25/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Increase machine space illumination to 19 ft-candles minimum 5/11/2023
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Increase machine space lighting to 19 ft-candles minimum 5/11/2023
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 x Provide shunt trip for mainline. Activated by a heat detector 5/11/2023
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 2.1.4 x Provide a means of smoke control in the hoistway compliant with the building code 5/11/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x The emergency/standby power shall be tested. 8/27/2024