A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Note: MCP is completely blank.
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
Machine room door shall be self-closing and self-locking. It does not self-close fully.
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. Note: No date tag.
|
|
A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.7.2 Seizing of Rope Ends
|
|
|
Suspension rope tail ends shall be properly seized/banded. Electrical tape is not proper.
|
|
A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.5 Wedge Rope Sockets
|
|
|
Hoist rope tail retaining clips shall be properly spaced.
|
|
A17.1-2016 : Elevators
|
3.17 - Door and gate equipment
|
8.6.4.13
|
|
|
Adjust upthrust roller bearings for proper clearance to door hanger track (multiple floors).
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall work (with and without main power) and give proper location.
|
2/22/2024
|