Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.5 Wedge Rope Sockets Hoist rope tail retaining clips shall be properly spaced.
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.7.2 Seizing of Rope Ends Suspension rope tail ends shall be properly seized/banded. Electrical tape is not proper.
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work (with and without main power) and give proper location. 2/22/2024
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 Machine room door shall be self-closing and self-locking. It does not self-close fully.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Note: MCP is completely blank.
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. Note: No date tag.
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Adjust upthrust roller bearings for proper clearance to door hanger track (multiple floors).