Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x B(11)/1.6.1/ : 2-WAY COMMUNICATION DEVICE SHALL WORK. (Dials repeatedly, never connects) 10/24/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x B(11)/1.6.1/ : 2-WAY COMMUNICATION DEVICE SHALL WORK. (Dials repeatedly, never connects) 10/24/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)6 Detector edge wired to cab lighting circuit. Edge shall work independent of cab lighting. 4/27/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)6 Detector edge wired to cab lighting circuit. Edge shall work independent of cab lighting. 9/10/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Repair damaged Hoistway door guides, 3rd floor 9/16/2021
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept dry. Remove rust from pit equipment , repaint, investigate/repair water leak 11/16/2022
MO Minimum : Elevators (I) - Pits (I)1 Pit Scavenger pump shall be removed 9/10/2020
MO Minimum : Elevators (I) - Pits (I)1 Pit Scavenger pump shall be removed 4/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.14 - Ventilation 2.14.2.3 Cab fan Shall work 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.14 - Ventilation 2.14.2.3 Cab fan Shall work 4/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.14 - Ventilation 2.14.2.3 Cab forced ventilation fan shall work, (2020&2021 vio) 4/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.14 - Ventilation 2.14.3.3 Cab forced ventilation fan shall work 4/27/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. (Cert on display expired 2019) 11/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x telephone will not call out 7/29/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2-way communication device shall work and give proper location. 9/10/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elev Co.) 11/16/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Machine Room Fire Extinguisher has been removed from room, replace 11/16/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Pit Scavenger pump shall be removed(2020&2021 vio) 4/27/2022