ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
2.7.1.1
|
|
|
Machine Room Ceiling panels need to be replaced (2nd violation: 2019 and 2020)
|
4/27/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
|
|
Resecure machine room smoke detector to ceiling (2nd violation: 2019 and 2020)
|
7/12/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)6
|
|
|
Detector edge shall work independent of cab lighting circuit (reinspection needed)
|
4/27/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit Scavenger pump shall be removed. Reinspection needed
|
4/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Remove oil pads from pit and clean pit
|
4/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly.
|
4/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.14 - Ventilation
|
2.14.3.3
|
|
|
Cab forced ventilation fan shall work
|
4/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.14 - Ventilation
|
2.14.2.3
|
|
|
Cab fan shall work (TKE quoted)
|
4/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
2.7.1.1
|
|
|
Machine Room Ceiling panels need to be replaced (2nd violation: 2019 and 2020)
|
9/10/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)6
|
|
|
Detector edge shall work independent of cab lighting circuit (reinspection needed)
|
9/10/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit Scavenger pump shall be removed. Reinspection needed
|
9/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Remove oil pads from pit and clean pit
|
9/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly.
|
9/10/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Machine Room shall have proper Fire Extinguisher, missing.
|
11/16/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept clean and dry. Remove rust from pit equipment , repaint, investigate/repair water leak.
|
11/16/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. Provided by Elev Co
|
11/16/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. (Cert on display expired 2019)
|
11/16/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-WAY COMMUNICATION DEVICE SHALL WORK. (Dials repeatedly, never connects
|
10/24/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Must make Emergency Light operable. 8.6.4.15
|
8/13/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Must make Emergency alarm operable. 8.6.4.15
|
8/13/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm shall work with power loss. (Faulty button)
|
9/16/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
8.6.4.13 Door Systems
|
x
|
|
Missing upthrust roller, 2nd floor door.
|
9/16/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-WAY COMMUNICATION DEVICE SHALL WORK. (Dials repeatedly, never connects
|
10/24/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Resecure machine room smoke detector to ceiling (2nd violation: 2019 and 2020)
|
9/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
telephone will not call out
|
7/29/2018
|