Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Install missing hall fire signage. It shall read "in case of fire..". 4/20/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) x A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 4/20/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27.1 Phase I Emergency Recall Operation After Device Actuation x x Activation of 1st and 3rd landing lobby smoke FAID shall initiate main landing recall. Repair and all FAID will need to be retested for proper operation. 4/20/2023