A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27.1 Phase I Emergency Recall Operation After Device Actuation Yes Yes Activation of 1st and 3rd landing lobby smoke FAID shall initiate main landing recall. Repair and all FAID will need to be retested for proper operation. 4/20/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Yes No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 4/20/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Yes No Install missing hall fire signage. It shall read "in case of fire..". 4/20/2023