Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 Provide machine room door to be self closing.
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Provide current year tested fire extinguisher in the elevator machine room.
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Room and Machinery Space Clean the machine room.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(d) Provide acceptance data tags on controller to be completed.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) MCP has no entries, update.
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Top of Cars Clean the car top.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean the pit.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage) Post Phase I instructions near the f/f switch in the lobby.
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Electric junction box, top of the hoistway, back wall (for seismic) missing cover, provide.