MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Cartop inspection station won't run up.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working. Bldg phone line.
|
11/18/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door closer broken.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door must be self-closing and self-locking
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
openings at top back corners of shaft large enough for birds to enter. 2 dead birds on cartop.. openings need to be sealed to prevent from reoccurring
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Pit sump hole needs cover.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Pit sump pump hole needs cover
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
water seeping in pit from wall corner needs to be sealed to maintain dry pit
|
|