A17.1-2016 : Elevators
|
6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators
|
2.27.3
|
x
|
x
|
when elev is shunt triped power goes off an then back on by its self
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.14 Occupant Evacuation Operation
|
x
|
|
battery lowering not working
|
|
|
A17.1-2016 : Elevators
|
6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators
|
2.27.3
|
x
|
x
|
Heat initiating device does not shunt the elevator. Battery backup restarts the unit.
|
3/18/2026
|