Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation MCP has no entries, update.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(d) Acceptance data tag on the controller is blank, update.
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Room and Machinery Space Clean the car top.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean the pit.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Provide testing of the elevator on emergency power. 3/12/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage) Post Phase I instructions near the f/f switch in the lobby.
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.26.2.34 Unexpected Car Movement Device Car top lock off bar switch not working properly, adjust as needed.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x On Phase II operations, the door close button on the COP is not working (inside panel button is ok). 3/12/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Provide Testing of the elevator emergency generator power
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x When on phase 2 fire service, the close door button on the car operating panel inside the car inoperable. Repair or replace button