A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
2.26.2.34 Unexpected Car Movement Device
|
|
|
Car top lock off bar switch not working properly, adjust as needed.
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage)
|
|
|
Post Phase I instructions near the f/f switch in the lobby.
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
|
|
MCP has no entries, update.
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(d)
|
|
|
Acceptance data tag on the controller is blank, update.
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
When on phase 2 fire service, the close door button on the car operating panel inside the car inoperable. Repair or replace button
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
On Phase II operations, the door close button on the COP is not working (inside panel button is ok).
|
3/12/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Provide Testing of the elevator emergency generator power
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Provide testing of the elevator on emergency power.
|
3/12/2024
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Clean the pit.
|
|
A17.1-2016 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Room and Machinery Space
|
|
|
Clean the car top.
|
|