Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.5 Yes No means shall be provided for condensation drainage from air cond. in machroom 2/13/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Yes No phone line verification not working 2/13/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.1 Emergency communications and alarm not functioning (Red Tag) Yes Yes phone not working 2/13/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Yes No pit ladder clearance less than 4.5 ins. from centerline ofrung to stop sw. 2/13/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Yes No pit ladder side rails shall have a clear dist of not less than 4.5 ins from their centerline to the nearest permanet object 2/13/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers Yes No sump pump cover not flush or level with the floor 2/13/2023