Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x Need to test Phase I & II fire service. Re-inspection required
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency generators shall be scheduled for testing. Re-inspection required 3/17/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Elevator did not run on emergency generator power, test failed, needs repaired. Re-inspection required
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Fire service shall be tested. Re-inspection required 3/17/2026