| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | 2.8.3.3.4(a) When sprinkers are installed in the elevator pit electrical equipment and wiring in the hoistway located less than 48 inches above the pit floor shall be weatherproof (Type 4 as specified in NEMA 250) | 3/19/2024 | |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | x | osv needs tested no seal or tag on unit |