Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working, no phone line to the location at time of inspection. 8/2/2023
MO Minimum : Elevators (H) - Machine Rooms (H)8 x Broken EMT connector on phone line conduit. 8/2/2023
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) x Replace motion activated light sensor with a conventional switch for machine room lighting. 8/2/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone not working.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Smoke detector at top of hoistway not programmed correctly. Car does not return to the recall floor. 8/2/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Machine room smoke detector not programmed correctly. Fire hat flashes, but car does not capture, and go to the alternate landing. 8/2/2023