MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
x
|
|
Broken EMT connector on phone line conduit.
|
8/2/2023
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Machine room smoke detector not programmed correctly. Fire hat flashes, but car does not capture, and go to the alternate landing.
|
8/2/2023
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
x
|
|
Replace motion activated light sensor with a conventional switch for machine room lighting.
|
8/2/2023
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Smoke detector at top of hoistway not programmed correctly. Car does not return to the recall floor.
|
8/2/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working, no phone line to the location at time of inspection.
|
8/2/2023
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working.
|
|