MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Testing is incomplete. The following items shall be tested: Fire alarm initiating devices, communication loss, door pressure, and fire service.
|
8/28/2023
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Fire caulk/fill holes and voids in hoistway walls and corners.
|
8/28/2023
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
x
|
|
Label the machine room disconnects with location, source, and breaker numbers. (Mains and lighting)
|
8/28/2023
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
2.7.5.1 - Check machine room for adequate lighting (not less than 200lux/19fc) at floor.
|
8/28/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
x
|
|
Compliant/required documentation & MCP shall be kept in equipment room (neat/organized and not on car top) including wiring diagrams, oil log, and fire service log, recorded monthly. Not present in the machine room at this time.
|
8/28/2023
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
Machine room shall have a proper fire extinguisher and shall have a current test tag.
|
8/28/2023
|
A17.1-2016 : Elevators
|
3.17 - Door and gate equipment
|
8.6.4.13
|
x
|
|
Adjust up-thrust roller bearings for proper clearance to door hanger track. (multiple floors)
|
8/28/2023
|