A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.10.2.2.2(v)
|
x
|
|
Mach brake and secondary Brake must be made to hold 125% of Capacity. 2.16.8 ( currently neither brake will hold 125%) must be re-tested after repairs are made.
|
1/24/2024
|
A17.1-2016 : Elevators
|
2.27 - Rope fastenings
|
2.20.9
|
x
|
|
Must Properly Seize wire rope ends. 2.20.9.7.2 ( currently end are taped with Electrostatic tape not the equivalent of Seizing wire as code requires))
|
1/24/2024
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.4
|
x
|
|
Pit floor needs to be channeled or sloped to sump pump as to not allow accumilation of water. 2.2.2.4 ( currently pit is holding 1" of water in front corners)
|
1/24/2024
|