Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.4 x Pit floor needs to be channeled or sloped to sump pump as to not allow accumilation of water. 2.2.2.4 ( currently pit is holding 1" of water in front corners) 1/24/2024
A17.1-2016 : Elevators 2.27 - Rope fastenings 2.20.9 x Must Properly Seize wire rope ends. 2.20.9.7.2 ( currently end are taped with Electrostatic tape not the equivalent of Seizing wire as code requires)) 1/24/2024
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.10.2.2.2(v) x Mach brake and secondary Brake must be made to hold 125% of Capacity. 2.16.8 ( currently neither brake will hold 125%) must be re-tested after repairs are made. 1/24/2024