A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Phase 1 and 2 fire service has been tested. The smoke and heat detectors shall be tested once installed/working.
|
8/17/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work with and without main power and shall operate per code.
|
8/17/2023
|
A17.1-2016 : Elevators
|
5.7 - Car frame and platform
|
2.15.5
|
x
|
|
2.15.5 - Finish the installation of the cab floor.
|
8/17/2023
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
x
|
|
Finish grouting door sills.
|
8/17/2023
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Heat and smoke detectors are not working properly and shall be tested.
|
8/21/2023
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
x
|
|
This is more than 1/4" gap on the hallway door sills.
|
8/21/2023
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating Certificate shall be displayed in elevator machine room.
|
|