Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators 3.27.1 x Control space and machine space smoke detectos do not recall the elevator. Reprogram and retest. 11/2/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27 x x Install smoke detector at top of the hoistway for Install smoke detector at top of the hoistway for Fire recall. Program and test. 11/2/2023
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Seal all hoistway penetrations 11/2/2023
A17.1-2016 : Elevators 3.17 - Door and gate equipment 3.11 x Provide Fire protection for 2nd floor landing door frame 11/2/2023
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 3.7.1 x machine/control room/space illumination is less than 19fc 11/2/2023