A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Seal all hoistway penetrations
|
11/2/2023
|
|
A17.1-2016 : Elevators
|
3.17 - Door and gate equipment
|
3.11
|
x
|
|
Provide Fire protection for 2nd floor landing door frame
|
11/2/2023
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
3.27
|
x
|
x
|
Install smoke detector at top of the hoistway for Install smoke detector at top of the hoistway for Fire recall. Program and test.
|
11/2/2023
|
|
A17.1-2016 : Elevators
|
6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators
|
3.27.1
|
x
|
|
Control space and machine space smoke detectos do not recall the elevator. Reprogram and retest.
|
11/2/2023
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
3.7.1
|
x
|
|
machine/control room/space illumination is less than 19fc
|
11/2/2023
|