Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. No extinguisher in room or immediately adjacent to door. Wall box was empty. 2/13/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation x A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Not to be stored on car top. 2/13/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Check machine room for adequate lighting (not less than 19 fc at floor). 2/13/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x FAID testing failed. Machine space heat detector failed to activate shunt. Take corrective action and re-test. 2/13/2024