A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
x
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Not to be stored on car top.
|
2/13/2024
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. No extinguisher in room or immediately adjacent to door. Wall box was empty.
|
2/13/2024
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Check machine room for adequate lighting (not less than 19 fc at floor).
|
2/13/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
FAID testing failed. Machine space heat detector failed to activate shunt. Take corrective action and re-test.
|
2/13/2024
|