Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 3.26.10 Auxiliary Power fails to bring the car down and open the doors when normal power is removed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars. The tops of cars shall be kept free of oil, water, dirt, and rubbish, and shall not be used for storing lubricants, spare parts, tools, or other items. Provide a space to store maintenance documentation.
A17.1-2016 : Elevators 3.27 - Crosshead Data Plate and Rope Data Tags 8.11.3.1.3(bb) 2.16.3 The Crosshead data plate shall list the weight of the complete car, including the car safety and all auxiliary equipment attached to the car, the rated load and speed, the name or trademark of the manufacturer and year manufactured, type of suspension mean, the number of suspension members, either the diameter or the width and thickness in millimeters (mm) or inches (in.), as applicable, and the elevator manufacturer’s required minimum breaking force per suspension member in kilonewtons (kN) or pound-force (lbf), as applicable
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 8.6.4.6 Emergency Brake Rescue unit does not lift the brake allowing the elevator to drift up.