Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Must Post Current state operating Cert. in Mach Room. 5.100(2) 4/4/2023
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept dry. Replace water damaged pit channels and Remove rust from other pit equipment , repaint, investigate/repair water leak before next annual inspection. 4/4/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Adjust upthrust roller bearings for proper clearance and replace damaged astragal (2nd landing) 4/4/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 Top emergency exit shall be properly secured. 4/4/2023