Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x A17.1-2016 8.10.2.2.1(q) STAND BY POWER OPERATION Operation of elevators equipped with emergency or standby power shall be inspected and tested for conformance with the applicable requirements ITEM 1.17 (2.27.2) 8/7/2023
A17.1-2016 : Elevators 1.20 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.10.2.2.1(y) x A17.1-2016 8.10.2.2.1(y) EARTHQUAKE OPERATION INOPERABLE (y) Earthquake Inspections and Tests. ITEM 1.20 EARTHQUAKE OPERATION NOT OPERATING, TO BE REPAIRED (8.4.10.1.3) 8/7/2023
A17.1-2016 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 2.26.4.1 x A17.1-2016 8.10.2.2.2(s)(1) CONTROLLER WIRING, FUSES, GROUNDING, ETC. 8.10.2.2.2(s)(1) ITEM 2.12 wiring (2.26.4.1) MIS-SIZED FLEX TO BOX CONNECTORS ON MAIN LINE DISCONNECT 8/7/2023
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 x A17.1-2016 2.8 PIPES, WIRING & DUCTS 2.8.3 2.8.3.3.4 Guard sprinkler head in pit. 8/7/2023