Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Telephone needs reprogrammed or replaced. | 10/19/2023 | |
A17.1-2016 : Elevators | 11.1 - Access to Machine Room/Machinery Space/Control Room/Control Space | 2.7.3 | x | ASME A17.1 Sec. 2.7.3.4.1 Access doors shall be (a) self closing (b) self locking. Machine room access door not installed. | 10/19/2023 |