A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
x
|
|
Emergency communications loss monitor shall work.
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Fire service must be tested and documented monthly.
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP, Repair/PM/Callback Logs for 2023 - 2025.
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.1.5
|
x
|
|
There are windows in the hoistway. Windows in the walls of hoistway enclosures are prohibited. Note: A completely new elevator was installed in an existing hoistway that had windows in it. Customer to apply for a variance.
|
12/28/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)15
|
x
|
|
Exterior hoistway windows shall be guarded to prevent entrance by fire or emergency rescue persons. Each such window shall be marked "Hoistway" in a readily visible manner. Note: Currently signage says "Shaftway" and signage is located below each window. Customer may apply for a variance.
|
12/28/2023
|