Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)15 x Exterior hoistway windows shall be guarded to prevent entrance by fire or emergency rescue persons. Each such window shall be marked "Hoistway" in a readily visible manner. Note: Currently signage says "Shaftway" and signage is located below each window. Customer may apply for a variance. 12/28/2023
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.5 x There are windows in the hoistway. Windows in the walls of hoistway enclosures are prohibited. Note: A completely new elevator was installed in an existing hoistway that had windows in it. Customer to apply for a variance. 12/28/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Emergency communications loss monitor shall work.
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP, Repair/PM/Callback Logs for 2023 - 2025.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Fire service must be tested and documented monthly.