MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
x
|
|
Pit electrical outlet missing cover.
|
5/23/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
Replace missing "Do not use elevator in case of fire" signage on multiple floors.
|
5/23/2024
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Car Emergency System (Re-Inspection)
|
x
|
|
Emergency lighting shall work with loss of main 120v power.
|
5/23/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell shall work with loss of main 120v power.
|
5/23/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall work. It dials out, but no answer.
|
5/23/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Acceptance test is incomplete. Need to test FAID.
|
5/23/2024
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
x
|
|
Disconnects shall be labeled with location of feeder breakers.
|
5/23/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
x
|
|
2.8.3.3 - Lobby fire alarm initiating devices shall not be within 3 feet of the HVAC vent.
|
5/23/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
x
|
|
2.8.3.3.4 - Pit fire alarm initiating devices shall not be below 48" from pit floor. Necessitates moving pit sprinkler to 24" above pit floor to maintain 24" heat to sprinkler relation.
|
5/23/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
x
|
|
2.8.3.3.2 - Sprinkler located at 2nd landing lobby shall have a FAID to shunt power before water flow (Machinery space when controller open).
|
5/23/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
x
|
|
2.8.3.3.2 - Sprinkler located at 2nd landing lobby shall have a FAID to shunt power before water flow (Machinery space when controller open).
|
6/26/2024
|