Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Main and lighting disconnects shall have feed locations labeled. 7/20/2024
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Provide code compliant fire extinguisher at/near machine space. 7/20/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 7/20/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Missing 4x4 electrical box cover is hoistway. 7/20/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine space lighting shall be at least 19 foot-candles at floor. 7/20/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x FAID test failed. Hoistway smoke did not recall. Heat detector on ML to be relocated to within 2' of sprinkler. 7/20/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Communication loss buzzer shall work. 7/20/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Pit light and outlet not working (1 of 3 fixtures). 7/20/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Repair hoistway fire penetrations/fire caulk. 7/20/2024