MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
Main and lighting disconnects shall have feed locations labeled.
|
7/20/2024
|
A17.1-2016 : Elevators
|
2.31 - Relief Valves
|
3.19.4.2
|
x
|
|
Relief valve to be properly adjusted and verified.
|
7/20/2024
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
There is no fire extinguisher located near the machine space.
|
7/20/2024
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Repair hoistway fire penetrations/fire caulk.
|
7/20/2024
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
FAID failed. Hoistway smoke did not recall. Heat detectors (2) on ML to be relocated to within 2 feet of sprinkler. Verify shunt.
|
7/20/2024
|